Thermolator
®
vacuTrac
Positive/Negative Pressure
Water Temperature Controller
with TW-1 or TW2 Microprocessor
Instant Access
Parts and Service
(800) 458-1960
(814) 437-6861
www.conairnet.com
The Conair Group, Inc.
One Conair Drive
Pittsburgh, PA 15202
Phone: (412) 312-6000
Fax: (412) 312-6227
Installation
Operation
Maintenance
Troubleshooting
Vista de página 0
1 2 3 4 5 6 ... 118 119

Resumo do Conteúdo

Página 1 - Thermolator

Thermolator®vacuTracPositive/Negative PressureWater Temperature Controllerwith TW-1 or TW2 MicroprocessorInstant Access Parts and Service(800) 458-196

Página 2 - MOLD LEAKS

Actual temperature of water supplied to the mold ishigher than the setpoint deviation limit allows.1. High deviation temperature is set too low. Incre

Página 3 - TPHF017/1101

IMS0002/0296 SERVICE INFORMATIONAPPENDIX A-1Conair has made the largest investment in customer support inthe plastics industry. Our service experts ar

Página 4 - CONTROLS

WARRANTY INFORMATION IMS0003/0796APPENDIX A-2EQUIPMENTGUARANTEEPERFORMANCEWARRANTYWARRANTYLIMITATIONSConair guarantees the machinery and equipment on

Página 5 - SPECIFICATIONS NOTES:

UGH015/0100 PLUMBING DIAGRAMSAPPENDIX B-1ThermocoupleHeaterThermocouplePurge Valve(optional)To ProcessFrom ProcessCooling Water InCooling Water OutCoo

Página 6 - SEQUENCE OF OPERATION

PLUMBINGDIAGRAMSPLUMBING DIAGRAMS UGH009/0499APPENDIX B-2Return ThermocoupleHeaterSupply ThermocoupleTo ProcessFrom ProcessCooling Water InCooling Wat

Página 7 - TROUBLESHOOTING A VTR UNIT

PUMPCURVESUGH015/0100 TECHNICAL INFORMATIONAPPENDIX C-1MTRSPSI FEETGallons/MinuteLiters/Minute55 7818049 6916043 6114037 5212030 4310024 358018 264012

Página 9

IMH001/0300 THERMOLATOR SPI COMMANDSAPPENDIX D-1The SPI commands supported by Conair Thermolator®moldtemperature controllers are listed in the followi

Página 10

Status, ProcessPoll: 0x20 0x40SPI STATUS WORDWord BIT position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0EEprom error SET SET*A/D converter error SET SET*

Página 11

IMH001/0499 THERMOLATOR SPI COMMANDSAPPENDIX D-3Status, Machine 1Poll: 0x20 0x42SPI STATUS WORDWord BIT position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Página 12 - Stopping the Thermolator

THERMOLATOR SPI COMMANDS IMH001/0499APPENDIX D-4Status, Machine 2Poll: 0x20 0x44SPI STATUS WORDWord BIT position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Página 14

Material Safety Data SheetAn explanation of the terms used in this document may be found in OSHA 29 CFR 1910.1200,which is available from OSHA regiona

Página 15

5. Fire and Explosion DataFire and explosionhazards:Mercury presents a slight fire and explosion hazard whenexposed to heat or flame. Mercury vapors a

Página 16 - TW-1 and TW-2

PD-1UGH015/0100 Thermolator TW-1 and TW-2●●Spare Parts Lists . . . . . . . . . .PD-1●●TW-1 Wiring . . . . . . . . . . . . . . .PD-5●●TW-1 Circuit Bo

Página 17 - Please record your

PUMP ASSEMBLIESNickle resistant seal, open drip proof type motorPart No. Description09000952 ¾ HP pump model 11C (with cast iron impeller)09000953 1 H

Página 18 - CONTENTS

RECOMMENDEDSPARE PARTSUGH015/0100 RECOMMENDED SPARE PARTSPD-3PUMPMOTORSPart No. Description09001403 ¾ HP 208/230/460V/3/60 ODP (Open Drip Proof)09000

Página 19

RECOMMENDEDSPARE PARTSRECOMMENDED SPARE PARTS UGH015/0100PD-4HEATER CONTACTORSPart No. Description20004401 Heater contactor for 9kW 208/230/460V200044

Página 20 - INTRODUCTION

UGH015/0100 TW-1 230/460V WIRING DIAGRAMPD-5

Página 21

1 2345678CONFIGURATIONDIP SWITCHOFFON43214321UNLDR 1/ VENT 2 SOL +UNLDR 1/ VENT 2 SOL UNLDR 2/ COOL 1 SOL +UNLDR 2/ COOL 1 SOL F

Página 22 - READ THIS SO NO

UGH015/0100 TW-2 230/460V WIRING DIAGRAMPD-72

Página 23 - 1-4 INTRODUCTION

TW-2 CIRCUIT BOARD UGH015/0100PD-81 2345678CONFIGURATIONDIP SWITCHOFFON43214321UNLDR 1/ VENT 2 SOL +UNLDR 1/ VENT 2 SOL UNLDR 2/ COOL 1 SO

Página 24 - DESCRIPTION

OPERATIONTHE TW-2 CONTROLActual values displayThe green window displays the temperatureat the middle of the mold. This temperatureis calculated as an

Página 25 - THERMOLATOR ?

Actual temperature of water supplied to the mold ishigher than the setpoint deviation limit allows.1. High deviation temperature is set too low. Incre

Página 28

Thermolator®TW-1 and TW-2Instant Access Parts and Service(800) 458-1960(814) 437-6861www.conairnet.comThe Conair Group, Inc.One Conair DrivePittsburgh

Página 29 - SPECIFICATIONS

It’s a good idea to record the model and serial number(s) ofyour equipment and the date you received it in the UserGuide. Our service department uses

Página 30

UGH015/0100 Thermolator TW-1 and TW-2TABLE OFCONTENTSINTRODUCTION . . . . . . . . . . . . . . . . . . .1-1Purpose of the User Guide . . . . . . . .

Página 31 - FEATURES AND

Thermolator TW-1 and TW-2 UGH015/0100TABLE OFCONTENTSMAINTENANCE . . . . . . . . . . . . . . .(continued)Performing System Tests . . . . . . . . . .

Página 32 - INSTALLATION

TEMPERATURE CONTROL UNITSThermolator®vacuTrac (VTR1-DI and VTR2-DI)Positive/Negative Pressure One Conair Drive ● Pittsburgh, PA 15202 ● 412-312-6000 ●

Página 33 - UNPACKING THE

1-1UGH015/0100 Thermolator TW-1 and TW-2●●Purpose of the User Guide . . . .1-2●●How the guide is organized . . . .1-2●●Your responsibilities as a use

Página 34 - PREPARING FOR

Thermolator TW-1 and TW-2 UGH015/01001-2 INTRODUCTIONThis User Guide describes the Conair Thermolator®TW-1 andTW-2 water temperature control units and

Página 35 - WATER SUPPLY

UGH015/0100 Thermolator TW-1 and TW-2INTRODUCTION 1-3We design equipment with the user’s safety in mind. You canavoid the potential hazards identified

Página 36 - PURGE VALVE

WARNING: Hazardous substanceThe electrical contactors in theThermolator have mercury contactors.Mercury is considered a hazardous sub-stance and must

Página 37

2-1UGH015/0100 Thermolator TW-1 and TW-2●●What is the Thermolator TW Series? . . . . . . . . . . . . . . .2-2●●Typical applications . . . . . . . .

Página 38 - TESTING THE

The Thermolator TW models circulate water at a temperaturehigher than the available water supply, to add or remove heatas needed to maintain a uniform

Página 39 - 3-8 INSTALLATION

Direct injection models maintain the process temperatureby electrically heating and injecting cool water supplied tothe Thermolator by a chiller, towe

Página 40 - CHANGING

HOW IT WORKS:CLOSED CIRCUITThermolator TW-1 and TW-2 UGH015/01002-4 DESCRIPTIONReturn ThermocoupleHeaterSupply ThermocoupleTo ProcessFrom ProcessCooli

Página 41 - PROTECTION

Return ThermocoupleHeaterSupply ThermocoupleTo ProcessFrom ProcessCooling Water InCooling Water OutVent LineCoolingValveReliefValveCooling HeatExchang

Página 42

SPECIFICATIONSThermolator TW-1 and TW-2 UGH015/01002-6 DESCRIPTIONCABINET STYLE REFERENCEHeater Voltage Selection Single Zone 2 Zone 3 ZoneDirect Inje

Página 43 - CONTROL POINT

TPHF017/1101FEATURESOne Conair Drive ● Pittsburgh, PA 15202 ● 412-312-6000 ● FAX 412-312-6227 ● www.conairnet.comTEMPERATURE CONTROL UNITSThermolator®

Página 44

SPECIFICATIONSUGH015/0100 Thermolator TW-1 and TW-2DESCRIPTION 2-7TW1TW2Zones(1, 2 or 3)Direct Injection (DI)Closed Circuit (CC)Isolated Circuit (IC)P

Página 45 - DEVIATION

High efficiency pumpsfrom 3/4 to 7.5 Hp. Siliconcarbide seals are standard.Pump seal flush linecontinuously cleans thepump seal for extended life.Inco

Página 46 - ACTIVATING SPI

3-1UGH015/0100 Thermolator TW-1 and TW-2●●Unpacking the boxes . . . . . . . . .3-2●●Preparing for installation . . . . . .3-3●●Connecting the water s

Página 47 - AUTO START

UNPACKING THEBOXESThermolator TW-1 and TW-2 UGH015/01003-2 INSTALLATIONCarefully remove the Thermolator and compo-nents from their shipping containers

Página 48

UGH015/0100 Thermolator TW-1 and TW-2INSTALLATION 3-3The Thermolator is easy to install, if you plan the location andprepare the area properly.Positio

Página 49

Motorized Cooling ValveIf you have the optional motorizedcooling valve, connect the coolingwater supply to the female 3/4inchNPT fitting on the valve.

Página 50 - OPERATION

A purge valve is available as an option on Direct Injection andClosed Circuit units only. This valve quickly evacuates fluidfrom the process circuit,

Página 51 - 4-2 OPERATION

Thermolator TW-1 and TW-2 UGH015/0100Before beginning, note the electrical specifications on thenameplate mounted to the side of the unit. The electri

Página 52 - TW-2 CONTROL

UGH015/0100 Thermolator TW-1 and TW-2INSTALLATION 3-7Turn on the cooling water supply and check forleaks.If any leaks appear, stop the test and fix th

Página 53 - LOCATION

Thermolator TW-1 and TW-2 UGH015/01003-8 INSTALLATIONINITIALSETUPThe factory-set parameters and operating modes will satisfymost applications. But you

Página 54 - ENTERING A

TPHO017/1101FEATURESOne Conair Drive ● Pittsburgh, PA 15202 ● 412-312-6000 ● FAX 412-312-6227 ● www.conairnet.comTEMPERATURE CONTROL UNITSThermolator®

Página 55 - STARTING THE

UGH015/0100 Thermolator TW-1 and TW-2CHANGINGTEMPERATUREUNITSThe temperature units are factory-set as degrees Celsius ordegrees Fahrenheit, as specifi

Página 56 - STOPPING THE

Thermolator TW-1 and TW-2 UGH015/0100The TW-1 and TW-2 Thermolators provide the ability to pro-tect system parameters from unauthorized changes during

Página 57 - MANUAL PURGE

UGH015/0100 Thermolator TW-1 and TW-2Press the RUN button to save the passcode.◆◆ The control will display “Pr OFF” to prompt you toremove power to t

Página 58 - PERATION 4-9

Thermolator TW-1 and TW-2 UGH015/0100TW-1 models control the process temperature based upon theaverage of the temperatures recorded at the supply (to

Página 59 - AUTO TUNE

UGH015/0100 Thermolator TW-1 and TW-2SELECTING THETEMPERATURECONTROL POINT(TW-2 ONLY)INSTALLATION 3-13Press the RUN button to save the control point.◆

Página 60

Thermolator TW-1 and TW-2 UGH015/01003-14 INSTALLATIONYou can establish a normal operating range around the processtemperature setpoint using the high

Página 61

UGH015/0100 Thermolator TW-1 and TW-2INSTALLATION 3-15TW-1 and TW-2 Thermolators provide SPI compatible supportfor RS-485 serial communications with

Página 62 - MAINTENANCE

If you have a TW-2 model, you can automatically start andstop the Thermolator from a remote switching or timingdevice that has power contacts rated 11

Página 63 - SCHEDULE

Set dip switch 4 to theON position.Close the electricalenclosure and restorepower to the unit.When Auto Start is enabled:◆ The Auto Start indicator li

Página 65 - RESERVOIR

One Conair Drive ● Pittsburgh, PA 15202 ● 412-312-6000 ● FAX 412-312-6227 ● www.conairnet.comTPHS017/1101 SPECIFICATIONSTEMPERATURE CONTROL UNITSTherm

Página 66 - AINTENANCE 5-5

4-1UGH015/0100 Thermolator TW-1 and TW-2●●TW-1 control . . . . . . . . . . . . . . . .4-2●●TW-2 control . . . . . . . . . . . . . . . .4-3●●Mounting

Página 67 - KEY/DISPLAY

All normal operating functions can be controlled from theTW-1 control panel. If you have the optional manual moldpurge, the control button is located

Página 68 - INPUT TEST

TW-2 CONTROLUGH015/0100 Thermolator TW-1 and TW-2OPERATION 4-3Purge ValveThe light indicates the operating status of the purge valve. Except inTest Mo

Página 69 - OUTPUT TEST

Thermolator TW-1 and TW-2 UGH015/01004-4 OPERATIONMOUNTING THETW-2 CONTROLIN AREMOTELOCATIONCAUTION: Improper use of the swivelingcontrol panel can da

Página 70 - MONITORS

UGH015/0100 Thermolator TW-1 and TW-2OPERATION 4-5TW-1 and TW-2 Thermolators have a security feature that pre-vents accidental or unauthorized changes

Página 71 - CALIBRATING

Thermolator TW-1 and TW-2 UGH015/01004-6 OPERATIONBefore starting the Thermolator, verify that the system hasbeen installed correctly for your applica

Página 72

UGH015/0100 Thermolator TW-1 and TW-2OPERATION 4-7STOPPING THETHERMOLATORYou must shut down the Thermolator whenever you:● Change the water hookups.●

Página 73 - OPERATING

Thermolator TW-1 and TW-2 UGH015/01004-8 OPERATIONTW-1 and TW-2 direct injection and closed circuit models canbe ordered with an optional purge valve,

Página 74 - TROUBLESHOOTING

UGH015/0100 Thermolator TW-1 and TW-2OPERATION 4-9The TW-2 direct injection models can be ordered with anoptional purge valve, which clears the proces

Página 75 - A FEW WORDS

You should perform an Auto Tune after the first two hours ofoperation and whenever process variables change (changes incooling water pressure, piping

Página 76 - CAUSE OF A

CONAIR THERMOLATOR VTR POSITIVE/NEGATIVE OPERATION1.0 PROCESS WATER CONNECTIONSPROCESS CONNECTIONSConnect the FROM PROCESS and TO PROCESS connection

Página 77 - SHUT DOWN

Press and (the Setpoint Select button)simultaneously to begin the Auto Tune. The Actual display will flash “At” and the current processtem

Página 79

5-1UGH015/0100 Thermolator TW-1 and TW-2●●Maintenance schedule . . . . . . . .5-2●●Accessing the Thermolatorenclosure . . . . . . . . . . . . . . . .

Página 80

Thermolator TW-1 and TW-2 UGH015/01005-2 MAINTENANCEPREVENTATIVEMAINTENANCESCHEDULEThermolator TW-1 and TW-2 water temperature controllersare essentia

Página 81 - 6-8 TROUBLESHOOTING

PREVENTATIVEMAINTENANCESCHEDULEUGH015/0100 Thermolator TW-1 and TW-2MAINTENANCE 5-3●●Annually (every 12 months)❒❒ Test and calibrate the unit’s contr

Página 82

The isolated, or totally closed, circuit models separate thecooling water from the process fluid, which is held in a reser-voir inside the unit. This

Página 83 - 6-10 TROUBLESHOOTING

TW-1 and TW-2 Thermolators provide a Test Mode that testsdisplays and keys on the control panel, as well as inputs andoutputs. The Test Mode also allo

Página 84

The Key/Display Test verifies the function of displays, LEDsand buttons on the control panel.Enable Test Mode.Press any key.If necessary, index to the

Página 85 - POWER UP

The Input Test verifies the function of inputs available on thevarious TW-1 and TW-2 models. Not all inputs are used on allmodels. The performance ev

Página 86 - REPLACING

OUTPUT TESTThermolator TW-1 and TW-2 UGH015/01005-8 MAINTENANCEThe Output Test verifies the function of outputs available onthe various TW-1 and TW-2

Página 87 - PUMP OVERLOAD

water level float switch will make, opening the COOLING/MAKE-UP (3/8”) solenoid valve, replacing thehot discharged water with cooler water.This unit’s

Página 88 - MOTHERBOARD

All output monitors on the Thermolator can be enabled or dis-abled permanently through the OM Enable/Disable Menu inTest Mode.You need to use this fea

Página 89 - CONTACTOR

TW-1 and TW-2 Thermolators use type “K” thermocouples tosense the temperature in the return and supply process lines.These thermocouples should be cal

Página 90 - THERMOCOUPLES

Press the up ▲▲key to begin calibrating.The controller displays the name of the current calibration(examples: 32 SC.L; 32 rC.L; 510 SC.H; or 510 rC

Página 91 - SOLENOID

You can see the total numbers of operation by accessing theTotal Operating Hours Log in Test Mode.Enable Test Mode.Press any key to display the first

Página 92 - EPAIRING

6-1UGH015/0100 Thermolator TW-1 and TW-2●●Before beginning . . . . . . . . . . . .6-2●●A few words of caution . . . . . . .6-2●●How to identify the

Página 93 - ELEMENTS

You can avoid most problems by following the recommendedinstallation, operation and maintenance procedures outlined inthis User Guide. If you do have

Página 94

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-3A status light that turns fromgreen to red indicates analarm condition.Most Thermolator malfun

Página 95 - REMOVING

Thermolator TW-1 and TW-2 UGH015/01006-4 TROUBLESHOOTINGSHUT DOWNALARMSAlarmThe cooling waterpressure is less than25 psi.Note: The unit will re-start

Página 96 - - 2 HP PUMPS

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-5AlarmThe actual tempera-ture of water supplied to theprocess exceeds the260° F safety switchli

Página 97 - 3 - 7.5 HP PUMPS

Thermolator TW-1 and TW-2 UGH015/01006-6 TROUBLESHOOTINGAlarmActual temperatureof water supplied tothe process is belowthe programmed 20° F safety lim

Página 98

Figure 1.

Página 99

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-7SHUT DOWNALARMSThe Thermolator has detected a problem that could lead to equip-ment damage or

Página 100 - WE’RE HERE

Thermolator TW-1 and TW-2 UGH015/01006-8 TROUBLESHOOTINGWARNINGALARMSAlarmThe Thermolatorwill not heat to thesetpoint temperature,or takes too long to

Página 101 - PPENDIX A-2

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-9WARNINGALARMSAlarmThe Thermolatorwill not cool down,or takes too long tocool down. The actu-al

Página 102 - DIAGRAMS

WARNINGALARMSThermolator TW-1 and TW-2 UGH015/01006-10 TROUBLESHOOTINGThe Thermolator has detected a problem that could lead to a shutdown condition i

Página 103

SYSTEMALARMSUGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-11AlarmRAM hardwarefailure.ROM, checksumfailure.COP failures.Illegal Opcode.through

Página 104 - ECHNICAL INFORMATION

Thermolator TW-1 and TW-2 UGH015/01006-12 TROUBLESHOOTINGTHERMOLATORWILL NOTPOWER UPIf you apply power to the Thermolator and the control panel doesno

Página 105

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-13CHECKING ANDREPLACINGFUSESIMPORTANT: Alwaysrefer to the wiring dia-grams that came withyour T

Página 106 - THERMOLATOR

Disconnect and lockout the main power.Open the electrical enclosure door. Turn the screwon the front panel counterclockwise to open.Locate the pump ov

Página 107 - SPI STATUS WORDS

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-15REPLACING THEMOTHERBOARDIMPORTANT: Alwaysrefer to the wiring dia-grams that came withyour The

Página 108

Thermolators use mercury displacement heater contactors.The heater contactors should be replaced if:● You have checked the amp draw on each of the thr

Página 109 - Status, Machine 2

OPERATIONTHE TW-1 CONTROLActual values displayThe green window displays the temperatureat the middle of the mold. This temperatureis calculated as an

Página 110 - 7439-97-6

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-17The Thermolator uses two type ‘K’ thermocouples to monitor supply and return process temperat

Página 111

Thermolator TW-1 and TW-2 UGH015/01006-18 TROUBLESHOOTINGEvery Thermolator has a solenoid valve assembly that controlsthe cooling water out flow. Clos

Página 112 - /DIAGRAMS

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-19Reassemble the valve and other components.Reassemble in reverse order. Seal all pipe fittings

Página 113 - SPARE PARTS

Thermolator TW-1 and TW-2 UGH015/01006-20 TROUBLESHOOTINGDisconnect and lockout the main power.Remove the top panel of the Thermolator.Remove the heat

Página 114

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-21Lift the heating element out of the heater tube.Lift the element straight up.Replace the heat

Página 115

Disconnect and lockout the main power.Shut off the cool-ing water in feed.Drain the unit ofall fluid. Removethe drain plugs at therear of the unit.Rem

Página 116 - IRING DIAGRAM

To replace a failed seal, you must disassemble the pump.Remove the impeller nut. Insert a screwdriver in oneof the impeller waterway passages and back

Página 117 - IRCUIT BOARD UGH015/0100

To replace a failed seal, you must disassemble the pump.Remove the impeller retaining assembly. Insert ascrewdriver in one of the impeller waterway pa

Página 118

UGH015/0100 Thermolator TW-1 and TW-2TROUBLESHOOTING 6-25Reattach the pump tothe volute case. Makesure you replace any dam-aged gasket or O-ringbetwee