III – The axes’ parameters
S900–II CAN and AXES Configuration
Version 2.0 |–>
PARAMETER Abbreviation Description Parameter
value
Corresponding function
1292
1306
MODULO_N1
MODULO_N2
Modulo value in 1/10 mm.
1 –> 999999
This parameter is used to associate a known and finite value to a defined position.
Example : 2000 encoder pulses are required for a cyclic system to return to its “zero
point”. In this case, you would choose :
1 – a 2000 modulo
2 – to declare the type of modulo axis (parameter 1291).
Default value :
0
Possible value : 1 –> 999999 Interaction with other parameters : 1291, 1305
1294
1308
VALINIT_N1
VALINIT_N2
Initialization value in
1/10 mm.
1 –> 999999
Absolution position corresponding to :
1 – Leading edge of an initialization cam (initialization by cam only)
2 – Conjunction of the signals from the initialization cam and the encoders Init.
pulse (initialization by cam and Init. pulse)
This value is only used if the axis has been declared as being measured with initialization (Parameter 1291)
Default value :
0
Possible value : 1 –> 999999 Interaction with other parameters : 1291, 1305
1296
1310
CONVERS_N1
CONVERS_N2
Encoder pulse conversion
coefficient in millimetres.
1 –> 25000
Associated with parameter 1298, it defines the conversion factor between the
metric units and the encoder pulses.
Default value :
0
Possible value : 1 –> 25000 Interaction with other parameters : 1298, 1312